Tests were conducted at the Phil Ferguson Structural Engineering Laboratory at the University of Texas at Austin under the supervision of Dr. Richard Klingner Spring/Summer 2005.
2 ½" Pos-I-Tie Self-Drilling Screw In Steel Studs
Tension Test
5 specimens were tested. Each consisted of a 16 gage steel stud with 1/2"
Denz-glass, 2" Styrofoam, 2" airspace, and a standard modular clay-masonry
veneer. The 2-1/2" long Pos-I-Tie self-drilling screw was drilled through
the Styrofoam and denz-glass into the steel stud. A 3/16" x 4" long
Hot Dipped Wire Tie was connected to the Barrel-Screw and mortared in the bed
joint of the veneer.
Also given, in inches, are the "plateau displacements" at which the
approximate maximum load level was first reached. This plateau displacement
is a general index of the deformation capacity of the tie system.
| Table 1 |
Tension Test - With TRIANGLE WIRE TIE |
![]() |
|
| sample | failure |
failure load , lbs
|
Plateau Displacement, inches
|
| 1 | screw pulled out of steel stud |
679
|
1.2
|
| 2 | triangle tie pulled out of bed joint |
605
|
1.2
|
| 3 | eye of screw fractured |
709
|
1.3
|
| 4 | eye of screw fractured |
756
|
1.4
|
| 5 | triangle tie pulled out of bed joint |
644
|
1.5
|
| AVERAGE |
679
|
|
|
| COV |
0.086
|
|
| Table 2 |
Tension Test - With SINGLE WIRE TIE |
![]() |
|
| sample | failure |
failure load, lbs
|
Plateau Displacement, inches
|
| 1 | Single-leg tie pulled out of bed joint |
350
|
1.8
|
| 2 | Single-leg tie pulled out of bed joint |
610
|
0.6
|
| 3 | Masonry unit cracked, single-leg pulled out of bed joint |
415
|
0.2
|
| 4 | Eye of screw "walked" to end of single-wire tie, tie straightened out |
270
|
0.4
|
| 5 | Eye of screw "walked" to end of single-wire tie, tie straightened out |
547
|
0.3
|
| AVERAGE |
438
|
|
|
| COV |
0.32
|
|
Tension Tests - Self-Drilling Screw to Steel Studs Summary
" Specimens with triangle ties are about 1.5 times as strong as the single-wire
ties, and are also much more consistent in strength.
" These ties are "adjustable two-piece anchors" under the definition
of MSJC Code Section 6.2.2.5.6, which requires that one such anchor be provided
for every 2.67 ft2 of wall area. Put simply, each tie must be responsible for
2.67 sq ft of wall. A typical high design wind pressure (components and cladding)
is 50 lb/ft2. Typical design loads per anchor, assuming a load factor of 1.6,
are therefore about 215 lb. Even the weaker of the two types of tie has strength
about twice this.
" Specimens with triangle ties sometimes failed by pullout of the tie from
the bed joint, and sometimes by fracture of the eye of the screw. In contrast,
the specimens with single-wire ties sometimes failed by pullout of the tie from
the bed joint, and sometimes by straightening out of the tie. This straightening
out ultimately limited the capacity of the single-wire ties to loads less than
what would probably have been required to fracture the eye of the screw.
" Because the specimens were loaded so that the stud could rotate, loads
were directed along the axis of the tie, and the closed eyes at the ends of
the Pos-I-Tie® screws were subjected to concentric loads only, with essentially
no shear or bending. As a result, the capacities corresponding to eye fracture
are quite high, about 700 lb (triangle ties). This is in contrast to loads corresponding
to the Tapcon Pos-I-Tie tests, and is discussed in the section dealing the CMU
tests.
" Specimens with triangle ties have plateau displacements much larger than
the specimens with single-wire ties. This is because the triangle ties are closed,
and the eye cannot slip off. In contrast, specimens with single-wire ties are
limited in displacement capacity by straightening out of the tie or slipping
of the eye of the screw along the bent end of the tie. Triangle ties are initially
stiffer than single-wire ties, because they have two wires rather than one.
" Examination of some specimens shows that the female-threaded portion
of the Pos-I-Tie can turn with respect to the embedded portion of the screw.
This does not seem to affect capacity, however. Capacity is much more affected
by the movement under load of the screw-eye of specimens with single-wire ties,
toward the free end of the tie.
2 ½" Pos-I-Tie Self-Drilling Screw In Steel Studs
Compression Test
5 specimens were tested. Each consisted of two 16 gage steel studs with 1/2"
Denz-glass, 2" Styrofoam, 2" airspace, and standard modular clay masonry
veneer. Two 2-1/2" long Pos-I-Tie self-drilling screws were drilled into
each stud. 3/16" x 4" long Hot Dipped Pos-I-Tie Triangle ties were
connected to the Barrel-Screws and mortared in the bed joints of the veneer.
(Entire wall was 3 masonry units wide x 9 high).
| Table 3 | Compression Test - With TRIANGLE WIRE TIE |
|
|
![]() |
| sample | failure |
failure load, lbs
|
Plateau Displacement, (total) inches
|
Plateau Displacement, (gap) inches
|
| 1 | buckling of ties |
1503
|
0.6
|
---
|
| 2 | buckling of ties |
1359
|
0.4
|
0.1
|
| 3 | buckling of ties |
1254
|
0.4
|
0.1
|
| 4 | buckling of ties |
1398
|
0.4
|
0.2
|
| 5 | buckling of ties |
1458
|
0.4
|
0.2
|
| AVERAGE |
1394
|
|
|
|
| COV |
0.069
|
|
|
| Table 4 | Compression Test - With SINGLE WIRE TIE |
|
|
![]() |
| sample | failure |
failure load, lbs
|
Plateau Displacement, (total) inches
|
Plateau Displacement, (gap) inches
|
| 1 | buckling of ties |
1286
|
1.5
|
1.5
|
| 2 | buckling of ties |
743
|
0.8
|
0.8
|
| 3 | buckling of ties |
1015
|
0.4
|
0.4
|
| 4 | buckling of ties |
1026
|
0.4
|
0.2
|
| 5 | buckling of ties |
936
|
0.6
|
0.4
|
| AVERAGE |
1002
|
|
|
|
| COV |
0.20
|
|
|
Compression Tests - Self-Drilling Screw to Steel Studs Summary
" All specimens failed by buckling of the ties. Failure loads are higher
for triangle ties than for single-leg ties, because triangle ties have two legs
rather than one.
" These ties are "adjustable two-piece anchors" under the definition
of MSJC Code Section 6.2.2.5.6, which requires that one such anchor be provided
for every 2.67 ft2 of wall area. Put simply, each tie must be responsible for
2.67 ft2 of wall. A typical high design wind pressure (components and cladding)
is 50 lb/ft2. Typical design loads per anchor, assuming a load factor of 1.6,
are therefore about 215 lb. For four anchors, the typical design loads would
be 4 times this, or 860 lb. Even the weaker of the two types of tie has a
strength exceeding this.
" In specimens with triangle ties, the total plateau displacement is due
primarily to deformation of the studs, with only slight contributions from the
flexibility of the ties. In contrast, in specimens with single-wire ties, almost
the entire total plateau displacement is due to closing of the gap. This is
due to the relatively high flexibility of the single-wire ties compared to that
of the triangle ties.
| Table 5 |
Tension Test - With TRIANGLE WIRE TIE CMU Positie Tapcon® screw in face shell aligned with the cross-web |
|
|
| sample | failure |
failure load, lbs
|
Plateau Displacement, (total) inches
|
| 1 | Fracture of eye |
489
|
0.2
|
| 2 | Fracture of eye |
344
|
0.1
|
| 3 | Fracture of eye |
454
|
0.3
|
| 4 | Fracture of eye |
405
|
0.3
|
| 5 | Fracture of eye |
404
|
0.4
|
| AVERAGE |
419
|
|
|
| COV |
0.13
|
|
| Table 6 |
Tension Test - With TRIANGLE WIRE TIE CMU Positie Tapcon® screw in face shell aligned with the empty cell |
|
|
| sample | failure |
failure load, lbs
|
Plateau Displacement, (total) inches
|
| 1 | Fracture of eye |
410
|
0.4
|
| 2 | Fracture of eye |
549
|
0.7
|
| 3 | Pullout of tie from bed joint |
785
|
1.0
|
| 4 | Fracture of eye |
572
|
0.3
|
| 5 | Fracture of eye |
404
|
0.6
|
| AVERAGE |
544
|
|
|
| COV |
0.29
|
|
|
Table |
Tension Test - With SINGLE WIRE TIE CMU Positie Tapcon® screw in face shell aligned with the cross-web |
|
|
| sample | failure |
failure load, lbs
|
Plateau Displacement, (total) inches
|
| 1 | Pullout of tie from bed joint |
364
|
0.4
|
| 2 | Fracture of eye |
599
|
0.2
|
| 3 | Fracture of eye |
419
|
0.3
|
| 4 | Fracture of eye |
613
|
0.4
|
| 5 | Fracture of eye |
517
|
0.3
|
| AVERAGE |
502
|
|
|
| COV |
0.22
|
|
|
Table |
Tension Test - With SINGLE WIRE TIE CMU Positie Tapcon® screw in face shell aligned with the empty cell |
|
|
| sample | failure |
failure load, lbs
|
Plateau Displacement, (total) inches
|
| 1 | Fracture of eye |
574
|
0.2
|
| 2 | Fracture of eye |
325
|
0.3
|
| 3 | Fracture of eye |
621
|
0.2
|
| 4 | Fracture of eye |
427
|
0.2
|
| 5 | Fracture of eye |
487
|
0.4
|
| AVERAGE |
487
|
|
|
| COV |
0.24
|
|
5/8" Pos-I-Tie Tapcon® Screw In CMU Tension Test Summary
" Practically all specimens failed by fracture of the closed eye at the
end of the Pos-I-Tie screw. This failure mode is essentially independent of
the type of tie or whether the tie is attached to the face shell of the CMU
or the web. It is therefore essentially the same for all four types of specimens
tested in this series.
" These ties are "adjustable two-piece anchors" under the definition
of MSJC Code Section 6.2.2.5.6, which requires that one such anchor be provided
for every 2.67 ft2 of wall area. Put simply, each tie must be responsible for
2.67 ft2 of wall. A typical high design wind pressure (components and cladding)
is 50 lb/ft2. Typical design loads per anchor, assuming a load factor of 1.6,
are therefore about 215 lb. Even the weakest of the four types of specimen
has strength about twice this.
" Examination of close-up photos of different specimens of this series
during testing suggests that in most cases, the screw eyes were subjected to
a combination of direct tension parallel to the axis of the screw, shear perpendicular
to the axis of the screw, and local bending due to the orientation of the tie
through the eye. Shear perpendicular to the axis of the screw arises when the
axis of screw is not perpendicular to the face of the CMU, and therefore not
exactly parallel with the direction of loading.
" Because the specimens in this series were loaded so that the CMU and
the veneer could not rotate freely, if the anchor were not perpendicular to
the surface of the masonry, shears could exist perpendicular to the axis of
the anchor, and would account for the lower capacity of the ties in CMU compared
with the ties in Steel Studs. For example, in Table 5 and Table 6, which show
failures for triangle ties by fracture of the eye, capacities are uniformly
about 60% of the capacities corresponding to eye fracture for the same type
of triangle tie in Table 1. Although the anchors and the failure modes are identical,
the presence of shear in the CMU series makes the capacities in that series
less than those in the Steel Stud test. It also makes the ties in the CMU fail
almost invariably by fracture of the screw eye, rather than by the other failure
modes noted for Steel Studs.
" It might be thought that because local bending decreases the fracture
load of the eye, and because local bending depends on the angle of the upright
portion of the tie, that control of that angle in production is important. This
is not the case, however. No matter what the initial angle is, the tie straightens
out and the angle changes as the load increases.
" Specimens with triangle ties have plateau displacements larger than the
specimens with single-wire ties. This is because the triangle ties are closed,
and the eye cannot slip off. The difference is less for the CMU tests than the
Steel Stud tests, because the ties in the CMU are prevented from rotating by
the manner in which the CMU and veneer are loaded. In contrast, specimens with
single-wire ties are limited in displacement capacity by straightening out of
the tie or slipping of the hook of the screw along the bent end of the tie.
Triangle ties are initially stiffer than single-wire ties, because they have
two wires rather than one.