HECKMANN BUILDING PRODUCTS INC.
1501 N. 31st Avenue
Melrose Park, IL 60160-2911
800-621-4140 and 708-865-2403
FAX: 708-865-2640
SUBMITTAL SHEET:
#425 WEDGE INSERTS (SHELF ANGLE INSERTS)
#427 ASKEW HEAD BOLTS
Standard Sizes:
Inserts: 5/8", 3/4", and 3/4" Long. Available in Plain
Malleable Iron or Hotdip Galvanized After Fabrication.
Bolts: 5/8" diameter x 1-1/2", 2", 2-1/2", and 3"
long.
3/4" diameter x 1-1/2", 2", 2-1/2", 3", and 3-1/2"
long.
Available in Plain, Electro Galvanized After Fabrication, or Hotdip Galvanized
After Fabrication. Bolts come with a nut and washer. Bolts extend 1/4"
less than above lengths when installed in inserts. Wedge Inserts should be installed
a minimum of 1-1/2" from the edge of the concrete.
![]() |
![]() |
| Insert Size | Cat No. | A | B | C | D | E (1) | F(3) |
| 5/8" | 425-5 | 2-1/4" | 1-1/32" | 1-15/16" | 3-5/8" | 1-5/8" | 1" |
| 15.9mm | 57mm | 26.2mm | 49.2mm | 92.1mm | 41.3mm | 25mm | |
| 3/4" | 425-6 | 2-5/16" | 1-3/16" | 2-1/2" | 3-7/8" | 1-3/4" | 1" |
| 19mm | 58.7mm | 30.2mm | 63.5mm | 98.4mm | 44.45mm | 25mm | |
| 3/4" Long | 425-6L(2) | 2-1/4" | 1-1/4" | 2-3/8" | 5-1/2" | 3" | 1" |
| 19mm | 57mm | 31.7mm | 60.3mm | 140mm | 76.2mm | 25mm |
(1) E is length of vertical adjustment for Askew head Bolts.
(2) Long Inserts provide greater adjustability and can be placed near bottom of concrete
beams. Anchor loops are 3-1/2" (89)mm above bottom of insert and can be secured to
bottom layer of beam reinforcing.
TEST 1
Method of Test: Two inserts of each kind were cast in concrete blocks intended to be of 3,000 psi compressive strength. Companion 6" x 12" cylinders tested at the time the inserts were tested showed an actual compressive strength of 3,010 and 3,280 psi. The inserts were cast flush with the 16" x 16" surface of blocks having a thickness of 10". A short length of 1/2" reinforcing bar was placed thru the insert loop in the concrete. Blocks were allowed to cure under room conditions for 28 days. Tests were made loading the bolts in two different directions, directly outward (perpendicular to the surface in which the inserts were cast Pullout), and also downward (parallel to the same surface Shear).
PULLOUT TEST: Bolts were loaded in a direction perpendicular to the surface with the bolts at the midpoint of the slots in the inserts.
| Insert | Max Load Lbs. | Failure |
| 5/8 | 9,320 lbs | Concrete Broke around the inserts, then the concrete block cracked in the vicinity of the reinforcing steel bar. Insert did not break. |
| 3/4 | 9,830 lbs | Concrete broke around insert body and cracked at reinforcing steel bar. Insert did not break. |
| 3/4 Long | 12,860 lbs | Lips along slot of insert broke. Concrete broke along side of body. Insert did not pull out of concrete. |
SHEAR TEST: The tests pulling in a direction parallel to the surface of the concrete were made with a heavy angle block bolted at the mid point of the slot of the insert. The load was applied 2" out from the surface of the concrete. This would place some tension on the bolt, but would primarily tend to force the bolt to slip downward in the slot. The following Results were obtained:
| Insert | Max Load Lbs. | Failure |
| 5/8 | 5,240 lbs | Bolt slipped in slot 1/16" |
| 6,600 lbs | Bolt slipped in slot 3/16" | |
| 7,600 lbs | Bolt slipped in slot 3/8". No failure in insert or concrete, but bolt was bending slightly. | |
| 14,000 lbs | Maximum Load. Concrete broke around body of insert. | |
| 3/4 | 7,600 lbs | Bolt slipped in slot 1/16" |
| 10,500 lbs | Bolt slipped in slot 3/16" | |
| 10,960 lbs | Bolt slipped in slot 3/8". No failure in insert or in concrete, but bolt was bending slightly. | |
| 11,100 lbs | Maximum Load. Threads stripped on bolt. | |
| 3/4 Long | 5,660 lbs | Bolt slipped in slot 1/16" |
| 7,140 lbs | Bolt slipped in slot 3/16" | |
| 7,840 lbs | Bolt slipped in slot 3/8". No failure in insert or in concrete, but bolt was bending slightly. | |
| 19,150 lbs | Maximum Load. Bold had slipped to bottom of slot and head sheared. |
TEST 2
Shear Test: METHOD OF TEST: ASTM E 488-76 Shear Strength of Anchor in Concrete. Parallel to Concrete Face from top of Anchor.
| Insert Size | 1 | 2 | 3 | Average |
| 5/8" | 6,060 lbs | 6,500 lbs | 6,570 lbs | 6,377 lbs |
| 3/4" | 7,040 lbs | 7,580 lbs | 7,230 lbs | 7,283 lbs |
| 3/4" Long | 9,050 lbs | 8,550 lbs | 8,580 lbs | 8,727 lbs |
Concrete Fractured in all specimens, but insert did not fail. Compressive strength of concrete used at 28 days was 5,860 psi.
TEST 3
Pullout Test: METHOD OF TEST: ASTM E 488-76 Test for Strength of Anchors in Concrete.
| Insert Size | 1 | 2 | 3 | Average |
| 5/8" | 4,450 lbs a | 4,800 lbs a | 4,600 lbs b | 4,650 lbs |
| 3/4" | 5,400 lbs b | 5,800 lbs b | 5,700 lbs a | 5,633 lbs |
| 3/4" Long | 6,900 lbs c | 8,300 lbs c | 7,100 lbs c | 7,433 lbs |
a: Snapped Hood - Cracked Insert Slot
b: Pulled Out - Insert Intact
c: Broke Concrete - Insert Intact. Concrete Strength 6,040 psi
TEST 4 - 3/4" Long Insert Only
Concrete was poured into molds measuring 11-1/2" x 20" x 20". One insert was imbedded in the center of each mold. The inserts were malleable iron to the ASTM A-47 Grade 32510 specifications. No additional reinforcement, such as hairpins or rebar, were used in the concrete or inserts. The concrete used was 5,000 psi high early mix with the following proportions:
Cement 830 lbs Sand 1,168 lbs SSD
Stone 1/2" 1,802 lbs SSD Water 2,75 lbs
Daracem 100 66 ounces
Pullout tests were performed 6 days later when the concrete had reached a compressive strength of 4,758 psi as recorded from laboratory testing of 6" x 12" cylinders.
A Pair of I-Beams were used to span the concrete molds with a steel channel acting as a bridge. The channel held a 30 ton hydraulic jack powered by a manual pump. A hardened 3/4-10 NC threaded rod ran through the jack and bridge threading into the nut in the insert. Pressure readings were obtained using a certified calibrated gauge connected to the pump. The inserts were pulled to failure:
| Specimen 1 11,030 lbs | Specimen 2 10,140 lbs |
TEST 5: Askew Head Bolt Test
Axial Tensile Results (Requirements = 64,000
PSI Min.)
Ultimate Tensile Strength
(Tensile Testing was performed in Accordance with ASTM-F606-98)
|
3/4" x 2" |
3/4" x 2-1/2" |
|
Average 75,833 |
Average 71,666 |

For additional information on Specifications of Shelf Angle Inserts refer to the following:
NCMA TEK 93 - National Concrete Masonry Institute - Curtain and Panel walls of Concrete Masonry. 1977
BIA TECH NOTE 28B - Brick Institute of America - Brick Veneer Panel and Curtain Walls. February 1980
ANSI B18.2.1 1965 revised 1970 - Askew Head Bolts - American National Standards Institute.
|
Heckmann Building Products Materials and Finishes: |
© Copyright 2003 Heckmann Building Products Inc.