HECKMANN BUILDING PRODUCTS INC.
1501 N. 31st Avenue
Melrose Park, IL 60160-2911
800-621-4140 and 708-865-2403
FAX: 708-865-2640
SUBMITTAL SHEET: #315 WELD-ON ANCHOR ROD AND TEST DATA
Welded to Steel Columns. Used with #316 Triangle
Ties or #318 Web Ties to attach CMU or Brick to the
Steel Columns.
Standard Size: 1/4" diameter x 9" Long
Overall
Offset is 3/8" and provides 4" vertical adjustment.
Available in Plain Steel, Mill Galvanized, Electro Galvanized
After Fabrication, Hotdip Galvanized After Fabrication, and Stainless Steel.
![]() ![]() ![]() |
TEST DATA
SIZE: #315 Weld-On Anchor Rods,
1/4" (6.35mm) diameter wire x 5" (127mm) long with 2" (50.8mm)
adjustment were tested with #316 Triangle Ties 3/16"
(4.7625mm) diameter wire x 3" (76.2mm) long in 1" (25.4mm) cavity
and 3/16" diameter wire x 4" (101.6mm) long in 2" (50.8mm) cavity.
TEST CONDITIONS: Wall sections 23-5/8" (600mm) wide x 17-5/8" (447.6mm) high 3-5/8" (92.07mm) thick were made from ASTM C216 Clay Brick, grade SW, Type FBS. The specimens were three units long x six units high. The Triangle Ties were positioned between the third and fourth layers, and at the vertical centerline of the test specimens. The mortar joints were 3/8" (9.525mm) to 1/2" (12.7mm) thick and the Triangle Ties were embedded 1-1/2" (38.1mm) in the bed joint. The type N mortar used had a compressive strength of 2,200 psi. The Weld-On Rods were attached to steel columns with four 1/4" (6.35mm) to 3/8" (9.525mm) welds (two at the top and two at the bottom). Testing was conducted by The Engineering Research Institute Iowa State University.
TEST RESULTS:
| Tension | Compression 1" cavity 3" triangle |
Compression 2" cavity 4" triangle |
|
| R.E.E.L Loads | 233 lbs | 731 lbs | 615 lbs |
| deflection | .050 in. (1.27 mm) |
.027 in (.686 mm) |
.032 in. (.813 mm) |
| R.E.M. Loads | 816 lbs | 1,159 lbs | 702 lbs |
| deflection | .308 in. (7.823 mm) |
.060 in. (1.524 mm) |
.041 in (1.041 mm) |
| Peak Loads | 816 lbs | 1,159 lbs | 727 lbs |
| deflection | .308 in. (7.823 mm) |
.272 in. (6.91 mm) |
.107 in. (2.718 mm) |
R.E.E.L. values indicate the end of the elastic region (initial straight line portion of the graph) and the start of the inelastic region. (R.E.E.L loads are those recommended to which the appropriate safety factors should be applied for the design values based upon elastic behavior.)
R.E.M. values indicate the load achieved at the end of the ductile (somewhat plastic) region of the load-deflection behavior, beyond which much larger deflections occur. The R.E.M is the load that the researchers felt was the appropriate "interpreted maximum" load. In most cases the peak loads beyond R.E.M. were due to highly inelastic behavior, rotations, contact bearing, or exaggerated deflections that one would not want to count as part of the correct specimen peak capacity. (R.E.M loads are those recommended to which the appropriate safety factors should be applied to arrive at the manufacturer's recommended design value based upon strength or limit states design.)
Peak Loads were taken from the graphs prior to a significant decrease in load or at an abrupt failure point.
Tension Test: The failure mode of the tension test was the elongation of the triangular tie and its eventual pullout from the mortar joint.
Compression Test: The primary failure mode was characterized by the deformation and buckling of the wire with a secondary failure mode of the mortar joint. As the load increased the Triangle Tie buckled upward or downward until it came in contact with the portion of the Weld-On Rod which was welded to the column.
| Unloaded View |
|
| Compression Failure Top view |
|
| Compression Failure Side view | ![]() |
|
Heckmann Building Products Materials and Finishes: Stainless Steel: |
© Copyright 2003 Heckmann Building Products Inc.